Tabla ampacidad cables

AWGArea mm2Diametro exterior aprox mmCobre 60°C TW UFCobre 75°C RHW THHWCobre 90°C TBS SA SIS
180.824---14
161.31---18
142.083.36152025
123.313.85202530
105.264.45303540
88.375.98405055
613.37.71556575
421.28.92708595
326.7-85100115
233.610.4695115130
142.4-110130145
1/053.4913.52125150170
2/067.4314.69145175195
3/085.0115.99165200225
4/0107.217.46195230260
25012719.44215255290
30015220.83240285320
35017722.11260310350
40020323.31280335380
50025325.49320380430
600304-350420475
700355-385460520
75038030.92400475535
800405-410490555
900456-435520585
1000507-455545615
1250633-495590665
1500760-525625705
1750887-545650735
20001013-555665750


FUENTE: NORMA OFICIAL MEXICANA NOM-001-SEDE TABLA 310-15 (B) PARA UNA TEMPERATURA AMBIENTE DE 30° C
VEASE 310-15(B)(2) PARA FACTORES DE CORRECCION DE AMPICIDAD CUANDO LA TEMPERATURA SEA DIFERENTE A 30° C
VEASE 240-4(D) PARA LIMITACIONES DE PROTECCION CONTRA SOBRECORRIENTE DEL CONDUCTOR.