Tabla ampacidad cables

Calibre AWGArea mm2Diametro exterior aprox mmCobre 60°C TW UFCobre 75°C RHW THHWCobre 90°C TBS SA SISAluminio 60°C UFAluminio 75°C RHW XHHWAluminio 90°C SA SIS RHH
180.824---14---
161.31---18---
142.083.36152025---
123.313.85202530---
105.264.45303540---
88.375.98405055---
613.37.71556575405055
421.28.92708595556575
326.7-85100115657585
233.610.46951151307590100
142.4-11013014585100115
1/053.4913.52125150170100120135
2/067.4314.69145175195115135150
3/085.0115.99165200225130155175
4/0107.217.46195230260150180205
25012719.44215255290170205230
30015220.83240285320195230260
35017722.11260310350210250280
40020323.31280335380225270305
50025325.49320380430260310350
600304-350420475285340385
700355-385460520315375425
75038030.92400475535320385435
800405-410490555330395445
900456-435520585355425480
1000507-455545615375445500
1250633-495590665405485545
1500760-525625705435520585
1750887-545650735455545615
20001013-555665750470560630


FUENTE: NORMA OFICIAL MEXICANA NOM-001-SEDE TABLA 310-15 (B) PARA UNA TEMPERATURA AMBIENTE DE 30° C
VEASE 310-15(B)(2) PARA FACTORES DE CORRECCION DE AMPICIDAD CUANDO LA TEMPERATURA SEA DIFERENTE A 30° C
VEASE 240-4(D) PARA LIMITACIONES DE PROTECCION CONTRA SOBRECORRIENTE DEL CONDUCTOR.